2 Hour Fire Rated Self Supporting Membrane Ceiling

Designed for projects where conventional suspended ceilings are not practical, a self supporting membrane ceiling provides reliable fire compartmentation while leaving the ceiling void unobstructed for mechanical and electrical services.

The 2 Hour Fire Rated Self Supporting Membrane Ceiling supplied by PROSAFE, based on the selected tested design, is constructed using either a single layer or two layers of 9mm PROMATECT®-H calcium silicate boards fixed to a steel framing arrangement with mineral wool insulation. Depending on the approved system configuration, the complete assembly provides an overall system thickness of up to 128mm.

Tested to BS 476 Part 22:1987 for non-loadbearing construction, the system provides 120 minutes of fire resistance when installed in accordance with the approved tested assembly. Configurations are available to provide fire protection from below only or from both above and below, achieving a Fire Resistance Level (FRL) of -/120/120.

Suitable for commercial, industrial, institutional and residential developments, this system offers a practical passive fire protection solution for both new construction and refurbishment projects.

The 2 Hour Fire Rated Self Supporting Membrane Ceiling is suitable for a variety of building types, including:

  • Commercial buildings

  • Industrial facilities

  • Institutional buildings

  • Residential developments

  • High rise buildings

  • Refurbishment and restoration projects

Technical Specifications

Title
Description
Fire Resistance
120 Minutes
Fire Exposure
From below only / Top and bottom
Fire Resistance Level
FRL -/120/120
Test Standard
BS 476 Part 22:1987 (Non loadbearing)
Board
PROMATECT®-H
System Type
Self Supporting Membrane Ceiling
System Thickness
Up to 128mm (based on selected tested system design)
Applications
Commercial, Industrial, Institutional and Residential Buildings
Acoustic Performance
STC 48 / Rw 47 dB (Configuration PH.14.12) ; STC 32 / Rw 33 dB (Configuration PH.14.12-A)

Frequently Asked Questions

Is this system tested?

Yes. This system has been tested to BS 476 Part 22:1987 for non-loadbearing construction and provides 120 minutes of fire resistance when installed in accordance with the tested assembly. It is supported by the relevant test documentation and is accepted for BOMBA submission where applicable.

Do fire rated systems require certificate renewal?

No. Building owners do not need to renew the fire test certification. The certification is maintained by the system manufacturer (PROMAT), while the installed system should always follow the tested assembly and manufacturer recommendations.

How much does this system cost?

The cost depends on factors such as the project size, ceiling dimensions and specification requirements. Contact PROSAFE for a project-specific quotation and technical advice here.

Why choose PROSAFE for passive fire protection systems?

PROSAFE supplies PROMAT fire rated systems that are rigid, lightweight, moisture resistant and supported by tested documentation. With a wide range of system options and practical technical support, we help make system selection easier for projects across Malaysia.

Can this ceiling system span more than 6 metres?

The published tested assemblies cover ceiling widths of up to 6 metres. Contact PROSAFE if your project requires a larger ceiling span here.

Which side of the ceiling provides fire protection?

Depending on the selected tested system, this ceiling can provide 120 minutes of fire resistance from below only or from both above and below when installed in accordance with the approved tested assembly.