Ducts (Cladding to Steel / Cladding)
Fire-rated duct protection systems designed to maintain the integrity and insulation of ventilation, smoke extract, and service ducts during fire exposure.
Available in two solutions — PROMATECT®-H and PROMINA® 60 — to suit a wide range of duct types, configurations, and fire performance requirements.
Both systems can be configured for internal, external, or combined fire exposure, and tested to BS 476: Part 24: 1987 (Duct Types A & B).
Applicable Product
Note: FRL */*/* (Fire Resistance Limit – *Stability / *Integrity / *Insulation)
Product | FRL 120/120/120 | FRL 240/240/240 |
|---|---|---|
PROMINA® 60 | ✓ | |
PROMATECT®-H | ✓ | ✓ |
PROMATECT®-H
Key Advantages
High fire resistance: Up to 240/240/240 (full insulation & integrity systems)
Thermal performance: Good insulation and temperature stability
Mechanical strength: Maintains shape and integrity under fire exposure
Versatile installation: Internal and external fire protection in one system
Tested to international standards: BS 476: Part 24: 1987
Important Notes
-
Fire exposure type: Ensure the system matches the required duct type (A, B, or both)
-
Support structure rating: Hanger supports and fixing points must have the same FRL as the duct system
-
Maximum hanger spacing: Not to exceed 2440 mm unless otherwise protected
-
Penetrations: Must be sealed in accordance with tested system details
-
Movement joints: Required for long ducts or areas expecting structural movement